Polar X | Coolant Distribution Units | CDUs

Transtherm’s Polar X can be built in the form of in-row or Ultra Skid Based (up to 10MW) to allow for current and future needs.
Standard designs can be altered to match specific client preferences. Plus, Transtherm has built its reputation on offering completely bespoke equipment when needed.

  • Leading cooling density with minimal footprint
  • Unique slider arrangement for easy pump and heat exchanger maintenance
  • All major maintenance from front CDU face
  • Schneider based PLC + HMI control system
  • 316 grade stainless steel fluid circuits
  • Option for 25 or 50 micron TCS filters
35_Years_Transtherm_Experience_Data_Centre

Heat Transfer & Heat Recovery Are In Our DNA

Since the late 1980s, we have designed and built custom pump skids paired with heat exchangers, filtration, and intelligent PLC control systems – fundamentally, CDUs and ERUs (Energy Recovery Units), for some of the world’s most demanding industries, including:

  • Pharmaceutical
  • Data Centres
  • Automotive
  • Petrochemical
  • Food & Beverage

Polar X | Coolant Distribution Units - Accelerated Heat Rejection Design for Data Centres​

Heat_Exchanger_HVAC_Data_Centre

Peak Thermal Efficiency

Leading performance at the closest approach temperature differentials

IE5_Efficiency_Fan_Pump_Transtherm

Latest IE5 Efficiency

Latest IE5 efficiency pump technology

Coolant_Distribution_Units_Data_Centre_Pump_Cooling

Slide-Out Maintenance

Unique Pump and heat exchanger slider design for easy maintenance

Coolant_Distribution_Unit_Liquid_Data_Centre

Full Front-Face Access

All pumps, heat exchanger, strainers and controls accessible from front face

Flow_Control_HVAC_Transtherm_CDU

Precision Flow Control

Standard fast acting 2-way valve or EPIV available

CDU_Harmonic_Filtration_Data_Centre

Advanced Power Protection

Options for active harmonic filtration and supercapacitor

Polar X | CDUs | Coolant Distribution Units - Performance

Transtherm Cooling Industries

Polar X 2600 CDU
  • Exceeds DSX Benchmark (Self-certification testing in progress)
  • 2,600 kW at 4°C ATD & 10°C ΔT on TCS & FWS
  • 2,600 kW (Full capacity maintained with 25% Propylene Glycol on both TCS and FWS)
  • 2N+1 Pump Redundancy (3 x 50% duty pumps for seamless 100% capacity)
  • Full-Bore Electromagnetic Flow Meter (+/- 1.5% accuracy)
  • Fully Integrated Enclosure-Housed FWS Filter With Bypass

NVIDIA DSX Baseline

Mainstream CDUs
  • Recommended Baseline
  • Recommended 2,500 kW (4°C ATD, 10°C ΔT on TCS & FWS)
  • Quoted 2,300 kW (0% glycol / wider FWS ΔT) drops to ~1,680 kW (~73% of literature)
  • Basic N+1 pump with reduced performance mode
  • Insertion / Paddle-type Flow Meter (~94% accuracy)
  • FWS Filter supplied loose for site fitting

Rack Capacity For The Polar X Range

Slide

AI Architecture / Platform

Typical Rack Power Demand (kW)

Liquid: Air Split Ratio

Liquid Load to CDU (kW)

Racks Served by Polar X 1350 In-row CDU (~1,350 kW)

Racks Served by Polar X 2600 In-row CDU (~2,600 kW)

Racks Served by Upcoming Polar X Ultra Skid Based CDU (Up to 9,600 kW)

Blackwell
(e.g., GB200 / GB300 NVL72)

130 kW

75 : 25

98 kW

13 Racks

26 Racks

N/A

Vera Rubin
(e.g., VR200 NVL72)

225 kW

80 : 20

180 kW

7 Racks

14 Racks

N/A

Rubin Ultra / Kyber
(e.g., NVL576)

600 kW

90:10

540 kW

N/A

4 Racks

17 Racks

Who are using Transtherm's Cooling solutions for data centres?

The Polar X | Coolant Distribution Units - 3-Step Project Accelerator

Provide us with just four data points:

  • TCS Circuit Fluid Temperatures
  • Heat Load per CDU (kW/MW)
  • TCS Circuit External Pump Pressure (kPa/psi)
  • Data Centre Site Location

We design all equipment and provide:

  • Detailed Technical Specifications
  • Equipment Drawings (.dwg & .stp)
  • Transparent Project Pricing
  • Annual Energy Consumption Report

We schedule a quick call to:

  • Walk through the technical offering
  • Review the energy & cost savings
  • Refine and finalise the proposal
Heat_rejection_Design_Data_Centre_Cooling

Up to 80%

Reduction in Design & Procurement Time

Up to 15%

Annual OPEX Savings via Optimisation

0%

Component Integration Risk

What Transtherm's Customers Say...